General Specifications
Parameters : Current, Voltage and Energy for each channel of 4 channels
Accuracy : +/- 1% of the range for Voltage (voltage range is 20V to 70V DC). +/- 1% of the range for Current (current range is 0 to 99.9A DC). +/- 1% of the range for Cumulative Energy
Resolution : 2 place decimal for Voltage and 1 for Current. 2 place decimal for Energy.
No. of Digits : 3 digits for Current and Voltage.
Input Supply : 20V to 70V DC, polarity independent
Size : 96mm (W) x 96mm (H) x 65mm (D)
Operating Principle : Micro-Controller based. Real time clock incorporated
Operating Temperature : 0 Degree C to +55 Degree C
Range of Operation
Voltage DC : 20v to 70v
Current DC : 0A to 99.9A
Inputs (4 Independent Channels)
DC Voltage: : 20V to 70V
DC Current: : The four channels DC current (0 to 99.9 A) provided to sense the current.
Display

Information displayed using LCD with back light Information displayed by automatic scrolling or manual scrolling

Communication

The DC EM communicates with other devices on a 2-wire optically isolated RS-485 link and uses the Mod bus RTU slave protocol.

Mounting

Wall mounted, mounting fixture provided. Optionally rack mounting can also be provided.